About the Three Phase Power Calculator
Calculate real power (kW), apparent power (kVA) and reactive power (kVAR) for a balanced three-phase system from line voltage, line current and power factor. Choose delta or wye to get the phase voltage and current.
Rotating phasors and waveforms show the three phases 120° apart and the current lag.
Frequently asked questions
How do I calculate three phase power?
P = √3 × V_line × I_line × power factor. 400 V, 10 A at 0.85 PF is about 5.9 kW.
What is the difference between delta and wye?
In wye (star) each phase sees V_line/√3 and carries the line current. In delta each phase sees the full line voltage and carries I_line/√3.
What is kVA versus kW?
kVA is apparent power, voltage × current. kW is real power, kVA × power factor; the remainder is reactive power in kVAR.