Mini tools

Three Phase Power Calculator

Free three phase power calculator for delta and wye (star). Real, apparent and reactive power from line voltage, line current and power factor.

About the Three Phase Power Calculator

Calculate real power (kW), apparent power (kVA) and reactive power (kVAR) for a balanced three-phase system from line voltage, line current and power factor. Choose delta or wye to get the phase voltage and current.

Rotating phasors and waveforms show the three phases 120° apart and the current lag.

Frequently asked questions

How do I calculate three phase power?

P = √3 × V_line × I_line × power factor. 400 V, 10 A at 0.85 PF is about 5.9 kW.

What is the difference between delta and wye?

In wye (star) each phase sees V_line/√3 and carries the line current. In delta each phase sees the full line voltage and carries I_line/√3.

What is kVA versus kW?

kVA is apparent power, voltage × current. kW is real power, kVA × power factor; the remainder is reactive power in kVAR.